Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -1- HA026248
2132i and 2116i
Temperature and Process Indicator and Alarm Units
Installing and Operating Instructions
D
IMENSIONS AND
I
NSTALLATION
Model 2132i
Model 2116i
E
LECTRICAL
C
ONNECTIONS
To install the indicator
Please read the safety information on pages 5 & 6 before
proceeding.
1. Prepare the panel cut-out to the size shown.
2. Insert the indicator through the cut-out.
3. Spring the panel retaining clips into place. Secure the indicator
in position by holding it level and pushing both retaining clips
forward.
4. Peel off the protective cover from the display
Unplugging the indicator
The indicator can be unplugged from its sleeve by easing the
latching ears outwards and pulling it forward out of the sleeve.
When plugging the indicator back into its sleeve, ensure that the
latching ears click into place to maintain the IP65 sealing.
10mm
(0.4in)
38mm
(1.5in)
(Not to
scale
)
Recommended minimum
spacing of indicators in
both sizes
Output ratings
Relay: 2A, 264Vac resistive
Logic: 9Vdc, 12mA (non-isolated from sensor input).
Over current protection
Use a maximum 2A fuse for the indicator supply and relay output.
A suitable fuse is EN60127 (type T).
Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5 mm
(16 to 22
AWG). Hinged covers prevent hands or metal making accidental
contact with live wires. The rear terminals screws should be
tightened to 0.4Nm (3.5lb in).
22.2
-0.0 +0.3
x 45
-0.0 +0.6
2132
OP1
OP2
Panel cut-out
24mm
(0.95in)
0.88
-0.0 +0.1
x1.77
-0.0 +0.02
103mm (4.01in)
48mm (1.89in)
Panel retaining clipsLatching ears
Inch
mm
Sensor
input
External
Relay module
-
Relay*
Output
Logic*
I/O
T/C
+
Alarm
ack/reset
OR
Pt100
mA
Model 2116
i
AA
Neutral
Line
L
N
AB
V-
V+
1B
1A
20-29Vac/dc
Low voltage supply
24
24
85-264Vac
2.49
External Relay
module
Neutral
Relay*
Output
Logic*
I/O
Line
Sensor input
T/C
+
-
Alarm
ack/reset
OR
Pt100
mA
Model 2132
i
AA LNABV- V+
1B 1A
85-264Vac
20-29Vac/dc
Low voltage supply
24 24
2.49
RUN
HOLD
2216
MAN
OP1
OP2
SP2
REM
48mm (1.89in)
Panel cut-out
45 x 45mm
-0.0 +0.6
1.77 x 1.77in
-0.00 +0.02
103mm (4.01in)
48mm
(1.89in)
Panel retaining clips
Latching ears
*Not fitted in indicator only units. Also terminals 1A and
1B not fitted in indicator only unit.
This indicator meets the European directives on safety and
EMC
Thank you for choosing the 2132i or 2116i indicator and alarm unit. It
will provide accurate measurement and display of temperature and
other process variables with up to two alarm outputs for operator alert
and process protection.
Models 2132i/AL and 2116i/AL are
Indicating alarm units
which
come with an alarm relay output and logic I/O fitted.
Models 2132i/ND and 2116i/ND are
Indicator only units
which
come without the alarm relay output or logic I/O fitted. Alarms can
still be configured and flashed as messages in the main display but
they will not be able to operate a physical output.
The indicator is supplied configured according to the ordering code
given on page 5. Check the coding on the side labels to determine
the configuration of your particular indicator.
ENG
Zobrazit stránku 0
1 2 3 4 5 6

Shrnutí obsahu

Strany 1 - 2132i and 2116i

Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -1- HA0262482132i and 2116iTemperature and Process Indicator and Alarm UnitsInstalling a

Strany 2

Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -2- HA026248OPERATIONSwitch on the indicator. Following a 3 second self-test sequence,y

Strany 3

Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -3- HA026248PARAMETER LISTSUse these lists to change: • The alarm setpoints •The alarm

Strany 4 - Logic only

Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -4- HA026248CONFIGURING THE INDICATORSelect configuration level to change: •The display

Strany 5

Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -5- HA026248ORDERING CODEThe indicator is supplied configured according to the ordering

Strany 6 - SERVICE AND REPAIR

Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -6- HA026248SERVICE AND REPAIRThis indicator has no user serviceable parts. Contact you