Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -5- HA026248
O
RDERING
C
ODE
The indicator is supplied configured according to the ordering code shown below.
Model
number
Function Supply
voltage
Manual Logic
I/O
Alarm
Relay
Output
Sensor
input
Setpoint
min
Setpoint
max
Units External
relay
module
Input
adaptor
2132i
2116i
T
ECHNICAL
S
PECIFICATION
Display 4 digit, green. 10mm high characters
Supply voltage High voltage unit: 100Vac -15% to 240Vac +10%, 48-62Hz. Power consumption: 5Watts maximum
Low voltage unit: 24Vdc or ac -15%, +20% DC to 62Hz, Power consumption: 5Watts maximum
Operating ambients 0 to 55
o
C. 5 to 95%RH, non condensing
Storage temperature -30
o
C to +75
o
C.
Output ratings Relay(isolated): Maximum: 264Vac, 2A resistive. Minimum: 12Vdc, 100mA
Logic I/O: 9Vdc at 18mA (non-isolated from sensor input). Can be used as alarm output or alarm acknowledge
input
Calibration accuracy
± 1
o
C or ±0.25% of reading whichever is greater
Cold junction compensation >30 to 1 rejection of ambient temperature change. Uses INSTANT ACCURACY
TM
cold junction sensing
technology to eliminate warm-up drift and respond rapidly to ambient temperature changes.
Input filtering Off to 999.9 seconds
EMC standards Generic emissions standard EN50081-2 and immunity standard EN50082-2 for industrial environments
Safety standard EN 61010. Installation category II. (Voltage transients on the power supply must not exceed 2.5kV). Pollution
degree 2. All isolated inputs and outputs have reinforced insulation to protect against electric shock.
Atmosphere Not suitable for use above 2000m or in explosive or corrosive atmospheres
Panel sealing IP65 (EN 60529), or NEMA 4X
S
AFETY AND
EMC I
NFORMATION
Safety
This indicator complies with the European Low Voltage Directive
73/23/EEC, amended by 93/68/EEC, by the application of the
safety standard EN 61010.
Electromagnetic compatibility
This indicator conforms with the essential protection requirements
of the EMC Directive 89/336/EEC, amended by 93/68/EEC, by the
application of a Technical Construction File. This indicator
satisfies the general requirements of the industrial environment
defined in EN 50081-2 and EN 50082-2.
GENERAL
The information contained in these instructions is subject to change
without notice. While every effort has been made to ensure the
accuracy of the information, Eurotherm Controls shall not be held
liable for errors contained herein.
Unpacking and storage
The packaging should contain the indicator, two panel retaining
clips, a 2.49Ω current sense resistor and this instruction leaflet.
If the packaging or the indicator are damaged, do not install the
product but contact your nearest Eurotherm Controls agent.
Continued on the next page
External relay module
XX Not fitted
R7 Fitted (Operated
by the logic
output)
Supply voltage
VH 85-264Vac
VL 20 -29V dc or ac
Alarm Relay Output
XX Disabled*
Non-latched alarms
FH High alarm 2
FL Low alarm 2
AL High alarm 2 &
low alarm 3
Latched alarms
HA High alarm 2
LA Low alarm 2
AA High alarm 2 &
low alarm 3
NW New alarm
Manual
XXX None
ENG English
FRA French
GER German
NED Dutch
SPA Spanish
SWE Swedish
ITA Italian
Sensor input Display range and
Setpoint min & max limits
Thermocouples
°
C
°
F
J Type J -210 to 1200 -340 to 2192
K Type K -200 to 1372 -325 to 2500
T Type T -200 to 400 -325 to 750
L Type L -200 to 900 -325 to 1650
N Type N -200 to 1300 -325 to 2370
R Type R -50 to 1768 -58 to 3200
S Type S -50 to 1768 -58 to 3200
B Type B 0 to 1820 32 to 3308
P Platinell II 0 to 1369 32 to 2496
Resistance thermometer
Z Pt100 -200 to 850 -325 to 1562
Custom downloaded inputs
C Type C -W5%Re/W26%Re
(default custom sensor)
0 to 2319 32 to 4200
D Type D - W3%Re/W25%Re 0 to 2399 32 to 4350
E E thermocouple -200 to 999 -325 to 1830
1 Ni/Ni18%Mo 0 to 1399 32 to 2550
2 Pt20%Rh/Pt40%Rh 0 to 1870 32 to 3398
3 W/W26%Re (Engelhard) 0 to 2000 32 to 3632
4 W/W26%Re (Hoskins) 0 to 2010 32 to 3650
5 W5%Re/W26%Re (Engelhard) 10 to 2300 50 to 4172
6 W5%Re/W26%Re(Bucose) 0 to 2000 32 to 3632
7 Pt10%Rh/Pt40%/Rh 200 to 1800 392 to 3272
8 Exergen K80 I.R. Pyrometer -45 to 650 -49 to 1202
Process inputs (linear)
M -9.99 to +80mV Scalable -999 to 9999
Y 0 to 20mA Scalable -999 to 9999
A 4 to 20mA Scalable -999 to 9999
V 0 to 10Vdc (
input adapter required)
Scalable -999 to 9999
Units
C
°
C
F
°
F
K Kelvin
X Linear input
Logic I/O
XX Disabled*
Logic input
AC Alarm ack/reset
KL Keylock
Non-latched alarms
FH High alarm 1
FL Low alarm 1
Latched alarms
HA High alarm 1
LA Low alarm 1
NW New alarm
Function
ND Indicator only*
AL Indicating alarm
unit
Input Adaptor
XX None
V1 0-10Vdc
A1 0-20mA sense
resistor (2.49
Ω
.
0.1%)
*If ‘ND’ (Indicator only) is
specified in the function field,
then XX must be entered in
the Logic I/O and alarm 2
relay fields.